Technical & Electrical

The Supracontrol SMS20 is a high-sensitivity smoke detection sensor based on the Winsen MP-2 sensing element. It provides reliable early-warning smoke detection for ICT, industrial, and commercial environments. Designed for seamless RS-485 integration with Supracontrol controllers, it combines industrial durability with centralized monitoring and alarm management.

ParameterValue
System
MCU32-bit ARM® Cortex® M0+ ultra-low-power microcontroller
FirmwareBare-metal architecture ‒ C-based firmware
Sensor specification
Sensor typeWinsen MP-2 smoke sensor
CharacteristicsTarget gas: C₃H₈ (propane), smoke Measuring range: 200–10,000 ppm equivalent Typical accuracy: ±1% after calibration in clean air
Physical
Status LED1× bi-color LED for indicating device power and system status - Blinking Green: Sensor is initializing (few seconds after power-up) - Solid Green: Sensor is operational - Solid Red: One or more sensor values are in an alarm state
BUS portConnector: 1× RJ45 Interfaces: RS-485 Protocols: SupraBUS (optional Modbus RTU) Features: Auto-discovery
Reset buttonPush button for device reset. Primarily used for factory reset and sensor reinitialization.
Power
Input voltage12 VDC nominal (8–15.5 V), with reverse polarity and over-voltage protection
ConnectorRJ45 connector with integrated Power over Cable (PoC) for combined power and data
ConsumptionUp to 0.4 W
Enclosure
MaterialBlack ABS plastic, min. wall thickness 2.5 mm, fine-textured surface
Dimensions (W × H × D)62 × 28 × 62 mm (2.44 × 1.1 × 2.44 in)
Weight35 g (0.077 lbs)
Mounting optionsIntegrated DIN rail mounting bracket (TS35/7.5 and TS35/15)
Operating environment
Temperature-20 to 80 °C (-4 to 176 °F)
Humidity10 to 90 %RH non-condensing
ProtectionIP30
Storage conditions
Temperature-30 to 90 °C (-22 to 194 °F)
Humidity0 to 95 %RH non-condensing
Packaging
MaterialDouble-wall corrugated fiberboard (E/B flute), fully recyclable
Dimensions (W × H × D)146 × 66 × 146 mm (5.75 × 2.6 × 5.75 in)
Weight125 g (0.275 lbs)
Management
Centralized Management System (CMS)The sensor connects to Supracontrol controllers via RS-485 bus and is centrally managed and configured through the Supracontrol Enterprise application. All measurement data and sensor status are sent to the platform for unified monitoring, logging, and configuration. Real-time sensor data is also accessible via the Supracontrol Mobile app.