Controller Settings

v2.20.1

The Device Settings dialog lets you configure a controller’s name, location, time settings, power inputs, network configuration, GPRS connectivity, and communication channels.

Path: Devices → Controllers → select a device → Settings

Note: A controller must be online to edit its settings. Modbus IP devices may be edited while offline. When bulk-editing, all selected devices must belong to the same business unit.

Opening device settings

Select one or more controllers in the Controllers grid and click the Settings button in the toolbar.

General tab

FieldDescription
NameDisplay name for this controller
DescriptionOptional notes
LocationAssign the controller to a location in the hierarchy
Time zoneThe time zone the device uses for timestamps and scheduling
NTP URLNetwork Time Protocol server address for automatic clock synchronisation
DST enabledEnable or disable daylight saving time adjustments
PoE / PPS / SPS / BATEnable or disable each power input supply independently
Note: If the selected location belongs to a business unit referenced by an automation rule, a warning listing the affected rules is shown. Reassigning the device may impact those rules.

Sync DB

The Sync DB button forces the controller to re-synchronise its configuration from the Supracontrol database. Use this after making configuration changes that the device has not yet applied, or when a device loses sync after a network interruption.

Network tab

FieldDescription
DHCPEnable to have the device obtain its IP address automatically. Disable to configure a static address
IP addressStatic IP address (when DHCP is off)
Subnet maskNetwork subnet mask (when DHCP is off)
GatewayDefault gateway address (when DHCP is off)
DNS 1 / DNS 2Primary and secondary DNS server addresses (when DHCP is off)
NetBIOS nameNetwork name broadcast via NetBIOS (when DHCP is off)
MAC addressThe device’s hardware MAC address - read-only

Network changes apply to the device first

Saving network settings sends the new configuration to the controller hardware before applying general settings. A confirmation dialog appears before the changes are sent. Incorrect network settings can make the device unreachable - verify the values carefully before confirming.

GPRS tab

The GPRS tab is shown only when the controller has a cellular module.

FieldDescription
Turned onEnable or disable the cellular link
APNThe carrier’s Access Point Name
UsernameAPN authentication username (if required by the carrier)
PasswordAPN authentication password (if required by the carrier)
Signal infoRead-only: current RSSI, BER, and mobile operator (shown when the link is active)
Note: GPRS changes are applied to the device hardware first, followed by any general settings. A confirmation dialog appears before changes are sent. GPRS settings cannot be bulk-edited.

Channels tab

The Channels tab is shown only when the controller exposes communication channels such as serial bus ports.

For each channel:

SettingDescription
BaudrateCommunication speed: 9600, 14400, 19200, 38400, 57600, or 115200 bps
ProtocolThe protocol used to communicate with devices on this channel

GPRS Info dialog

To view the current cellular link status without opening full settings, select a controller with an active GPRS connection and click GPRS Info in the toolbar. The read-only dialog shows: IP address, RSSI, BER, firmware version, IMEI, and mobile operator.

Bulk editing

When multiple controllers are selected, the bulk edit dialog restricts editable fields to those that can safely be applied across all selected devices:

FieldBulk editable
LocationYes - optionally cascade to all attached peripherals
Time zoneYes
NTP URLYes
DSTYes
DHCP on/offYes
Power inputsYes
Network details (IP, subnet, DNS, etc.)No
GPRS settingsNo
Channel settingsNo

Enable Apply location change to peripherals to cascade the new location to all sensors attached to the selected controllers.